PMD3051F Water Pressure Transmitter is a pressure signal measured with atmospheric pressure (low pressure side) as the reference end, with one or two ends] as flange (or other connection mode) and process pipe connection. On the basis of ordinary pressure / differential pressure transmitter, one or two isolation film boxes are added to measure the liquid receiving part. It is mainly used to measure high temperature, easy curing or crystallization, containing solid suspended matter, too viscous, corrosive or other need to maintain hygienic conditions.
Parameter :
Medim | liquid, gas, or steam |
Measurement range | 0~2100Kpa (0~210mH2O), customized as request |
Output signal | 4 ~ 20mA dc, superimposed HART, RS485 |
Power supply | 24V dc. , power range 12V ~ 45V |
Accuracy | + 0.1%, + 0.075% |
Stability | + 0.2% ≤ 12 months of the maximum range |
Temperature range |
electronic:-40 ~ 85 °C,sensitive element:-40 ~ 204 °C, storage temperature: -40 ~ 85 °C. |
Temperature effect | + 0.2% ≤ 20 °C with zero and range temperature error of maximum range |
Power effect | less than 0.005% / V of the output range. |
Vibration effect | on any axis, the frequency is 200Hz and the error is + 0.05% / g of the maximum range. |
Load effect | as long as the voltage of the input transmitter is higher than 12V, there is no load effect in the load working area. |
Explosion-proof type | flameproof ExdIIBT5Gb; Intrinsic safety ExiallCT4/T5/T6Ga; |
Flange | DN25, DN40, DN50, DN80, DN100 (ANSI, DIN) |
Process pressure | PN16/25, PN40, PN64, PN100 |